EVI DC Inverter Heat Pump for heating and cooling
Heating Capacity: 8.7KW--75KW.
Air Cooled Chiller Specification

Model PW030-KFLRDC-D PW050-KFLRDC-D PW080-KFLRDC-D PW120-KFLRDC PW150-KFLRDC PW300-KFLRDC
Cooling Rated Capacity kW 7.2  11.6  16.7 24 30 63
Rated Power Consumption kW 2.7  4.5  6.6 9 10.9 23
EER W/W 2.67  2.58  2.53  2.67  2.75  2.74 
Heating Rated Capacity kW 8.7 14.2 22.9 30 37 75
Rated Power Consumption kW 2.3 3.8 6.7 9.3 10.9 21.9
COP W/W 3.78  3.74  3.42  3.23  3.39  3.42 
Capacity Adjust % 0~100 0~100 0~100 0~100 0~100 0~100
Rated Current A 15 26 30 18 19 38 
Max. Current A 20 35 40 25.5 34 71 
Power supply 220V 1N~/50Hz 380V 3N~/50Hz
Electric shock resistance
IP Code IPX4
Refrigerant R410A
Ambient range -30~43
Pipe diameter DN25(female thread) DN25(female thread) DN25(female thread) DN32(male thread) DN40(male thread) DN65(Flange)
Circulating water m3/h 1.2  2.0  2.9  4.1  5.2  10.8 
Water pressure drop kPa 46 50 56 60
Compressor Type Rotary Inverter  Scroll Inverter
Compressor Qty 1 1 1 1 1 2
Air discharge direction Side Top
Fan type   Low noise axial fan
Air Flow m3/h 2500 2500*2 3500*2 5000*2 15000 13000x2
Sound level dB(A) ≦54 ≦56 ≦60 ≦62 ≦62 ≦62
Unit weight kg 135 155 205 300 400 700
Dimension L mm 1050 1050 1050 1300 1020 2000
W mm 480 480 480 580 980 1000
H mm 800 1330 1330 1450 1870 1900

Remark:
Rated cooling conditions:  ambient dry bulb 35℃/ wet bulb 24℃, inlet temperature 12℃, outlet temperature 7℃.
Rated heating conditions: ambient dry bulb 7℃/ wet bulb 6℃, inlet temperature 40℃, outlet temperature 45℃.
Note: the parameters of some products have changed in the process of continuous optimization. Please refer to the actual products.
inquiry
Leave your phone number in your mailbox, we will call you within 24 hours
  • Submit